|
|
 |
|
 |
|
by Paul Cook
of the Institute of Electrical Engineers
You
do not have to earth plastic pipes
Plastic pipes
make for a safer electrical installation and reduce the need for
earthing. Festooning an installation that has been plumbed in plastic
pipe with green and yellow earth wire is not necessary and of likely
to reduce the level of electrical safety of the property, not increase
it.
Everyone knows
that water and electricity do not mix, that the risk of electric
shock is greater when there is water around. They know that the
risk and severity of an electric shock is increased as a result
of the presence of water. This may be the reason for the concern
that water in plastic pipes may conduct electricity and that bonding
is required. Because of this, the IEE commissioned the Electrical
Research Association to carry out measurements of the electrical
conductivity of water in plastic pipes.
The ERA tests
confirm that tap water in a plastic pipe is a poor conductor of
electricity. One metre of 15mm diameter of plastic pipe filled with
tap water from Leatherhead where the ERA are based, has resistance
of 100,000 Ohms. This one metre of 15mm pipe will restrict currents
to less than fatal values and of course in practice, there would
be many metres of pipe between metal items of plumbing equipment
and earth.
The resistance
of water varies around the country, it is reduced by impurities,
not all of which are harmful. The additives put into water of central
heating systems to reduce corrosion make the most difference, as
can be seen from the table below.
|
|
Resistance - Ohms |
| 15mm
diameter, tap water |
115.000 |
| 20mm
diameter, tap water |
65,000 |
| 15mm
diameter, tap water with double dose of inhibitor at 60 deg.
C |
20,200 |
|
|
So why do wet
hands and immersion in a bath increase the risk of electric shock?
The human body
plus clothes, particularly shoes has an impedance of about 3,000
Ohms - see next table. At 230 volts this will result in a current
of about 153mA (153 thousandths of an amp). This is not nice, but
is unlikely to kill you. If there are no shoes and hands are wet,
the impedance falls to 500 Ohms and the current at 230 volts is
460mA. This is getting decidedly unpleasant. Immersion of the body
in a bath, in effect halves the impedance of the body and current
at 230 volts would be then 1,000 mA. This is dangerous, and can
kill.
|
|
Siliation
|
Body
Impedance
|
Current
at 230 V
|
|
Dry
with shoes
|
3000
+ Ohms
|
76
mA
|
|
Dry
|
1500
Ohms
|
153
mA
|
|
Wet
|
500
Ohms
|
460
mA
|
|
Body
1/2 immersed
|
250
Ohms
|
920
mA
|
|
|
Normally dry hands
and feet are quite good insulation. However, if the hands are wet,
salts and contaminants improve the contact and reduce the resistance
of the skin. Dry skin has a high resistance, wet skin has a relatively
low resistance.
The other reason
why bathrooms and such places are relatively risky electrically,
is the presence of earthed metal. Should you be unfortunate enough
to touch the live parts of broken equipment and nothing else except
say a well insulated floor, there would be little result. Electrical
jointers and fitters regularly work live under such controlled conditions.
However if you touch a live part and an earthed metal pipe, then
you get a very dangerous electric shock.
An earthly
environment where there are lots of metal pipes is potentially less
safe than an earth free environment. We can now start to see why
plastic pipe installations are going to lead to safer installations.
For a start, there is not all that earthed metal around.
The bonding
requirements for plastic piped and metal pipes installations is
described below.
At
the Service Position - Main Bonding
In each electrical installation, main equipotential bonding
conductors (earthing wires) are required to connect to the main
earthing terminal for the installation of the following:
|
 |
metal
water service pipes |
 |
metal
gas installation pipes |
 |
other
metal service pipes and ducting |
 |
metal
central heating and air conditioning systems |
 |
exposed
metal structural parts of the building |
 |
lightning
protection systems |
|
|
It is important
to note that the reference above is always to metal pipes. If the
pipes are made of plastic, they do not need to be main bonded.
If the incoming
pipes are made of plastic, but the pipes within the electrical installation
are made of metal, the main bonding must be carried out. The bonding
being applied on the customer side of any meter, main stopcock or
insulating insert and of course to the metal pipes of the installation.
The connections
of the bonding wired to the pipes has to be made with a proper clamp
to BS 951 complete with the label "SAFETY OF ELECTRICAL CONNECTION
- DO NOT REMOVE."
If the incoming
services are made of plastic and the pipework within the building
is of plastic then no main bonding is required. If some of the services
are of metal and some are plastic, then those that are of metal
must be main bonded.
|
 |
|
In
the bathroom - Supplementary Binding
Supplementary
or additional equipotential bonding (earthing) is required in locations
of increased shock risk. In domestic premises the locations identified
as having this increased shock risk are rooms containing a bath
or shower (bathrooms) and if you are lucky to have one, in the areas
surrounding swimming pools.
Please note,
there is no specific requirement to carry our supplementary bonding
domestic kitchens, wash rooms and lavatories test do not have a
bath or shower. That is not to say that supplementary bonding in
a kitchen or wash room is wrong (it would be wrong for plastic pipes!)
but it is not necessary.
For plastic
pipe installation within a bathroom the plastic pipes do not require
supplementary bonding and metal fitments attached to these plastic
pipes also would not require supplementary bonding.
It seems to
to be the practice of some builders to effect all the plumbing in
plastic except for those bits of the pipework that are visible.
These short lengths of metal pipework supplied by plastic pipes
or metal taps connected to plastic pipes, metal baths supplied by
plastic pipes and with a plastic waste do not require supplementary
bonding.
However, electrical
equipment still does require to be supplementary bonded and if an
electric shower, or radiant heater is fitted, they will require
to be supplementary bonded as usual.
This requirement
does not apply to class II or all insulated equipment where no metal
work that is likely to become alive in the event of a fault, is
accessible. However, it is recommended that supplementary bonds
are run to the earth terminals of all electrical equipment accessories
e.g. flex outlets, or the equipment itself, as class II equipment
may be replaced by class I during the life of the installation.
Figure 1 shows
the supplementary bonding in a bathroom where the house is plumbed
with metal pipes and figure 2 shows the supplementary bonding required
in a bathroom where the pipework is plastic.
Metal radiators
supplied by plastic pipes should not be supplementary bonded. It
is safer not to supplementary bond them. Locations generally are
safer if the location is earth free as discussed earlier.
|
 |
|
Figure1: Supplementary
bonding in a bathroom - metal pipe installation
Notes:
1. All simultaneously accessible metal (class I) equipment (e.g.
electrical heaters and showers), central heating pipes, hot and
cold water and waste pipes require supplementary bonding in or close
to the bathroom.
2. Metal baths
not connected to a metal building structure do not require supplementary
bonding if all metal pipe connected to them has been connected.
3. Connections
to pipes to be made with BS 951 clamps (complete with "Safety
Electrical Connection" label).
|
 |
|
Figure1: Supplementary
bonding in a bathroom - plastic pipe installation
Notes
1. Metal (class I) items of equipment (e.g. electrical heaters and
showers) require supplementary bonding if simultaneously accessible.
Supplementary bonds to be connected to the protective conductors
of each circuit at the accessory point.
2. Supplementary
bonding of short lengths of copper pipe(less than 0.5m in length)
installed where the pipes are visible, is not necessary.
There are many
possible combinations of metal and plastic pipe arrangements in
a bathroom. To try and answer questions regarding the supplementary
bonding required in a number of permutations of copper and plastic
pipe, table A has been prepared.
|
| Pipework
Material |
Supplementary
bond required between |
Comments |
| |
Waste
Pipes |
Cold
Water |
Hot
Water |
Central
Heating |
| 1 |
Metal |
Metal |
Metal |
Metal |
All
metal pipes, earth terminals of class I equipment, and accessible
exposed-conductive parts of the building structure |
Metal
pipes can be used as bonding conductors if joints are metal
to metal and electrically continuous |
| 2 |
Plastic |
Plastic |
Plastic |
Plastic |
Earth
terminals of class I equipment and accessible exposed-conductive
parts of the building structure |
Bonding
of metal taps, metal radiators or metal baths is not required
unless the bath is connected to the metallic building structure |
| 3 |
Plastic |
Plastic |
Metal |
Metal |
Hot
water pipes, central heating pipes, earth terminals of class
I equipment and accessible exposed-conductive parts of the building
structure |
A
bond is not required to the taps, nor metal baths unless connected
to the metallic building structure |
| 4 |
Plastic |
Plastic |
Plastic |
Metal |
Central
heating pipes, the earth terminals of class I equipment and
access to exposed-conductive-parts of the building structure |
Bonding
of metal water taps is not required, nor metal baths unless
connected to the metallic building structure |
| 5 |
Plastic |
Metal |
Metal |
Metal |
All
metal pipes, earth terminals of class I equipment, and accessible
exposed-conductive parts of the building structure |
Metal
pipes themselves can be used as bonding conductors if joints
are metal to metal and electrically continuous |
| 6 |
Plastic |
Metal |
Metal |
Plastic |
All
metal pipes, earth terminals of class I equipment, and accessible
exposed-conductive parts of the building structure |
Metal
central heating radiator does not require bonding |
|
| Notes: |
| 1. Supplementary
Bonding is carried out to the earth terminal of equipment within
the bathroom with exposed-conductive part. A supplementary bond
is not run back to the main earth |
3. Metal
baths are supplied by metal pipes do not require supplementary
bonding if all the pipes are bonded and there is no other connection
of the bath to earth |
| 2. Metal
window frames are not required to be supplementary bonded unless
they are electrically connected to the metallic structure of
the building |
4. All
bonding connections must be accessible and labeled "Safety
Electrical Connection - Do Not Remove". |
|
|